Oil vs Dry Type Transformer: Which one for your Australian site?

The choice between an oil-filled transformer and a dry-type transformer comes down to four factors: voltage rating, installation location, fire safety requirements and maintenance budget. Oil-filled units handle higher voltages up to 750 kV and are suitable for outdoor installations. Dry-type transformers are limited to about 72kV but are safer for indoor and high-fire-risk environments.

At Ampcontrol, we have been designing and building oil-immersed and dry transformers for more than 50 years, supplying mining operators, utilities, data centre developers, and large industrial sites across Australia. In this article, we break down a clear, framework so you can make the right decision for your site.

The Comparison Between Oil Filled vs Dry Type Transformers

What is a dry-type transformer?

A dry-type transformer is an electrical transformer that uses natural air, sometimes combined with solid insulation such as cast resin or epoxy, as both the cooling medium and the insulating medium. The coil and iron core sit inside a ventilated steel enclosure, or are fully encapsulated in resin.

With no insulating oil in play, dry-type transformers rely entirely on air convection and the dielectric strength of the solid insulation to keep windings electrically isolated and thermally protected. Air is a less efficient cooling medium than oil, which is why dry transformers are generally limited to medium voltage applications (up to ~35 kV) and lower kVA ratings.

Sub-types of dry-type transformers

Vacuum Pressure Impregnated (VPI) wound transformers are impregnated with class H polyester resin under vacuum and pressure for high dielectric and mechanical strength. Vacuum Pressure Encapsulated (VPE) units run the same process with a thicker insulation coating for harsh environments. Cast resin (cast coil) transformers fully encapsulate the windings in epoxy, offering excellent resistance to moisture and chemical contamination, and are common in indoor commercial sites.

Open-wound transformers expose the coils to maximise airflow in clean ambient conditions. Flameproof dry-type transformers are a specialised variant designed to suppress arc explosions in hazardous environments - used extensively in Australian underground coal mining.

Where dry-type transformers are used in Australia

Dry-type transformers carry the load in shopping centres, hospitals, schools, office towers, hyperscale data centres, manufacturing plants, and underground hard rock and coal mining (flameproof variants). They are increasingly the default for renewable energy generation and BESS containerised installs where fire safety is a planning condition. Across these outdoor applications and indoor installations, dry transformers offer lower fire risk and require less maintenance - both important when a site is located inside a public building or in a remote location.

What is an oil-filled transformer?

An oil-filled transformer, also called an oil-immersed transformer or liquid transformer, uses insulating fluid as both the cooling medium and the dielectric. Most oil transformers run on mineral oil. A growing share uses ester fluid (natural FR3 or synthetic) or silicone. The transformer's core and windings sit inside a sealed steel tank filled with the fluid.

Heat generated by the secondary windings and the magnetic core is transferred to the fluid, which circulates by natural convection, or by pumped flow in larger oil-filled units, to cool the assembly. Oil-filled transformers excel in high-voltage and large-scale industrial applications where dry transformers cannot meet the required voltage levels.

Sub-types of oil-filled transformers

Conservator (free-breathing) units use a separate expansion tank to accommodate oil expansion as temperature changes - standard for larger utility transformers on transmission and distribution lines. Sealed-type oil-filled units maintain a nitrogen cushion above the oil to prevent moisture ingress and insulation breakdown - popular for distribution applications.

Pad-mounted oil transformers are ground-mounted with tamper-resistant enclosures and are used in commercial and light industrial contexts. Pole-mounted units are smaller distribution-line transformers mounted on utility poles to deliver last-mile electrical energy.

Where oil-filled transformers are used in Australia

Oil-filled units handle the bulk of high-voltage applications in Australian electrical power systems: utility-scale step-up and step-down at substations, distribution networks, mine-site surface power infrastructure, large industrial sites, transmission grid components, and renewable energy generation step-up at solar and wind farms.

Anywhere the voltage rating exceeds about 35 kV, oil-immersed transformers are usually the only viable choice.

How to Choose Between Oil-filled and Dry-type Transformers

Engineers choose between these two transformer types based on seven factors. 

[H3] 1. Voltage rating and capacity

This is a hard technical limit, not a preference. Dry-type transformers cap out around 35 kV because air and solid insulation cannot match the cooling capabilities of insulating oil at high voltage. Oil-filled transformers can be scaled to 750 kV and beyond because oil circulates through the iron core and windings, removing heat at much higher rates. 

Above 35 kV, the choice is made for you - you need an oil-immersed unit. Below 35 kV, both are viable, and the next six factors decide.

2. Installation location and environment

  • Indoor commercial is usually dry type

  • Outdoor substation is oil-filled

  • Underground coal mining is flameproof, dry type (mandatory)

  • Outdoor in extreme ambient temperature is oil-filled (better thermal performance and overload capacity)

  • Coastal or corrosive environment,  either works, but enclosure rating and protection class matter more than transformer type

3. Fire safety and risk tolerance

Mineral oil burns. Ester fluid resists ignition through a much higher fire point. Dry types eliminate the risk of liquid fire entirely. Modern data centres (which must comply with AS 1851 fire compliance and operator-level fire policies), hospitals, public buildings, and basement installations are increasingly mandating dry-type transformers.

Outdoor substations with bunding and fire suppression continue to use oil-filled units as standard. The lower fire risk of dry transformers has been the single biggest driver of indoor adoption over the last five years.

4. Maintenance regime and total cost of ownership

A 1,500 kVA oil-filled transformer in continuous service requires DGA testing every 12 months, oil filtration every 3–5 years and full oil replacement around year 15. An equivalent 1,500 kVA dry-type transformer operating in the same application requires annual visual inspection and cleaning every 2–3 years. Even with a higher initial cost, the dry type often wins on total cost of ownership over a 25-year horizon - but this inverts at higher capacities where the upfront premium grows.

5. Footprint, weight and transportation

Oil-filled transformers are more compact per kVA but significantly heavier (oil weight). Dry-type transformers are larger per kVA but lighter - easier to crane into place on retrofit projects. For greenfield substations, footprint usually wins (oil-filled). For retrofit into existing rooms, weight and door access usually decide.

6. Environmental and sustainability requirements

For organisations with ESG commitments or Scope 3 reporting obligations, dry type or ester fluid is increasingly the default. Mineral oil carries spill, oil leakage, contamination and end-of-life disposal liabilities that ester fluid and dry-type units do not. 

The energy efficiency story is closer than most expect - modern dry-type transformers and modern oil-immersed units both meet AS/NZS 60076 efficiency requirements - so the differentiator is environmental risk, not no-load losses.

Need help specifying the right transformer for your site?

Ampcontrol has been designing and manufacturing oil-filled and dry-type transformers in Australia for more than 50 years. Our engineering team works directly with mining operators, utilities, data centre developers and industrial sites to specify, manufacture and commission transformer assets that comply with AS/NZS 60076.

We supply oil-filled, ester-fluid, and dry-type units across the medium-voltage and high-voltage range, plus flameproof dry-type variants for underground coal mining. Explore Ampcontrol's full Power Transformers range for product specifications across kVA ratings, voltage levels and protection classes. Talk to our team about commissioning, maintenance, refurbishment and DGA oil testing.

Frequently asked questions

What is the difference between a dry and a liquid-filled transformer?

The core difference is the cooling medium. A dry-type transformer uses natural air and solid insulation (cast resin or VPI) to cool and isolate the windings. A liquid-filled transformer - also called an oil-immersed transformer- uses insulating oil (mineral, ester or silicone) for the same job. The cooling medium drives every other difference: voltage capability, fire risk, footprint, maintenance and cost.

Are dry-type transformers better than oil-filled?

Neither is universally better. Dry-type transformers are better for indoor installations under 35 kV, where fire safety, low maintenance, and environmental risk dominate the decision - commercial buildings, data centres, and hospitals. Oil-filled transformers are better for outdoor applications above 35 kV - utility substations, transmission, large industrial sites - because they handle higher voltage and offer better cooling efficiency.

Do dry-type transformers contain oil?

No. Dry-type transformers contain no insulating oil and no transformer oil of any kind. They use natural air or sealed air as the cooling medium and rely on solid insulation - cast resin, VPI, or open-wound construction - to keep the windings electrically isolated. The absence of flammable liquids is the reason they are suitable for indoor and fire-sensitive applications.

When should you use an oil-filled transformer?

Use an oil-filled transformer when you need higher voltage than 35 kV, when the unit is installed outdoors, or when efficient cooling at high kVA capacity is critical. Power stations, transmission and distribution lines, utility substations, solar and wind farm step-up units, and heavy industrial smelters all default to oil-filled units because dry-type cooling cannot keep up.